1MODELS SBN71120NE THRU SBN85390NE/A Series 108COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER• INSTALLATION • OPERATION • MAINTENANCE • LIMIT
10MODEL - 250Input: 250,000 Btu/hr Total Vent Height (Feet)Vent Connector Size: 6 inches 6 8 10 15 20 30 50 100Input Btuh/hr Rise Vent Connector Diam
11MULTIPLE HEATER MANIFOLDFigure 8 and tables on pages 9 and 10 should be used forhorizontally manifolding two or more heaters. FIGURE 8WATER LINE
12INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGEUse of the top inlet water connection requires installation of aninlet dip tube (refer to figure 9). T
13VERTICAL STORAGE TANK AND FORCED CIRCULATION DANGERTEMPERATURE SETTING SHOULD NOT EXCEED SAFE USETEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CON
14 DANGERTEMPERATURE SETTING SHOULD NOT EXCEED SAFE USETEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 25. IF HIGHER PREHEAT T
15INSTALLATION DIAGRAMS-SIDE INLET/OUTLET USAGE DANGERTEMPERATURE SETTING SHOULD NOT EXCEED SAFE USETEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CO
16ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURESTORAGE WITH OR WITHOUT RECIRCULATIONHEATER WITH OR WITHOUT MIXING VALVEHEATER WITH MIXING VALV
17TWO TEMPERATURE - TWO PRE-HEATERS WITH MIXING VALVE OR BOOSTERHEATER WITH OR WITHOUT BUILING RECIRCULATIONTWO PRE-HEATERS WITH MIXING VALVETWO PRE-H
18MEDIUM TEMPERATURE - ONE HEATER WITH AUXILIARY STORAGE TANK FORCEDCIRCULATION WITH OR WITHOUT BUILDING RECIRCULATIONVERTICAL STORAGE TANKHORIZONTAL
19MANIFOLD KITSTWO UNIT MANIFOLD KIT(PART NO. 78692)THREE UNIT MANIFOLD KIT(PART NO. 78593)FOUR UNIT MANIFOLD KIT(PART NO. 78694)MODEL DIMENSION “A”SB
2 TANK APPROX U.S Gallons/Hr. and Litres/Hr at TEMPERATURE RISE INDICATED CAPACITY EFF. F° 36F° 40F° 50F° 54F° 60F° 70F° 72F° 80F° 90F° 1
20HEATER WIRINGAll electrical work must be installed in accordance with the latestversion of the National Electrical Code ANSI/NFPA No. 70, mustconfo
21GAS PIPINGContact your local gas service company to ensure that adequategas service is available and to review applicable installationcodes for your
22correct water column pressure allowing for a nominal pressuredrop through the controls.The minimum gas supply pressure for input adjustment mustnot
23SEQUENCE OF OPERATIONThe following information will describe the Sequence ofOperation for this appliance.1. Switch power on to unit.2. Thermostat ca
24A. This appliance does not have a pilot. It is equippedwith an ignition device which automatically lights theburner. Do not try to light the burne
25WATER TEMPERATURE CONTROL DANGERTHIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLETHERMOSTAT TO CONTROL WATER TEMPERATURE. HOTWATER TEMPERATURES REQ
26Servicing of the ignitor assembly includes keeping the ignitorfree of lint, scale or any other foreign debris.FIGURE 12, IGNITORMAIN BURNERThe main
27When the heater is operating at full capacity, or full gas input, itshould consume 1 cu. ft. of gas in time indicated on Table 9.VENTING SYSTEMExami
28Hydrochloric base acids are not recommended for use on glasslined tanks. CAUTIONObserve handling instructions on label of product being used.TANK CL
29Note: If your container does not have the vent cap and ventboss, drill a 3/16" hole in the handle. When you have finisheddeliming you will be
3TABLE OF CONTENTSROUGH-IN-DIMENSIONS -------------------------------- 2FOREWORD ------------------------------------------------- 3GENERAL SAFETY INF
30REPLACEMENT PARTS, SERVICE HANDBOOKS AND TRAINING AIDSReplacement parts may be ordered through State dealers, authorized servicers or distributors.
31 REMEDYCOMPLAINT CAUSE USER SERVICEMAN*W
32500 Lindahl ParkwayAshland City, TN 37015Phone: 800-821-2017 Fax: 800-644-9306www.stateind.com
4GENERAL SAFETYINFORMATIONPRECAUTIONSDO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDERWATER. Immediately call a qualified service technician to in
5HIGH ALTITUDE INSTALLATIONS WARNINGINSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIREREPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCEWITH SECTION 8.1.
6 IGNITION CONTROL BOARDFIGURE 4EXHAUST INDUCER (BLOWER ASSY.)All SBN 120-400 models are equipped with an exhaust induce
7any direction. If the heater is installed in a carpeted alcove, theentire floor shall be covered by the panel. Also, see the DRAININGrequirements i
8HARD WATERWhere hard water conditions exist, water softening or thethreshold type of water treatment is recommended. This willprotect the dishwasher
9TYPE B GAS VENTMultiple Gas Fired Tank-Type HeatersWhen venting multiple tank type heaters using Type Bvent pipe, follow the installation diagram (fi