1PLACE THESE INSTRUCTIONS ADJACENT TO HEATER ANDNOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.PRINTED IN U.S.A. 0303 PART NO.195092-000COMMERCIAL OIL F
10OPERATIONGENERALNever operate the heater unless the tank is filled with water and atemperature and pressure relief valve is installed.FILLING1. Oil
11 DUAL-BULB THERMOSTAT (COVER REMOVED)FIGURE 17BURNER CERTIFICATE (COMBUSTION TEST)The Commercial Standard CS75 Oil Burner Certif
12SEDIMENT REMOVALWater borne impurities consist of fine particles of soil and sand whichsettle out and form a layer of sediment on the bottom of the
13• Observe interior through opening - a small flashlight may be usedeffectively.• If the interior still shows water scale, the deliming process shoul
14ONE TEMPERATURE - ONE HEATER VERTICAL STORAGE TANK FORCEDCIRCULATION WITH OR WITHOUT BUILDING RECIRCULATIONSCALD PREVENTIONHOT WATER CAN SCALD IF US
15SINGLE TEMPERATURE OR BOOSTERTWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGEWITH OR WITH OUT RECIRCULATIONRETURN LINE FROM 180°F (82.2°C)CIRCU
16TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE STORAGEWITH OR WITHOUT RECIRCULATION* PIPE RELIEF VALVE TO OPEN DRAINNOTE: IF TEMPERED WATER IS RECI
17TWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER)WITH OR WITHOUT CIRCULATIONTWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HE
18TWO TEMPERATURE-ONE HEATER HIGH TEMPERATURE STORAGEWITH RECIRCULATION OF SANITIZING LOOPNOTE 1: TOGGLE SWITCH CONTROLS 180°F WATER CIRCULATION.INSTA
19THREE UNIT MANIFOLD KIT (PART NO. 78693)FOUR UNIT MANIFOLD KIT (PART NO. 78694)CHECK LIST AND SERVICEINFORMATIONIMPORTANTThe installer may be able t
2TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATIONRELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFOREUSING APPLIANCE.This is a typical oil-fired
208. Burner may not be firing at proper rate.• Check nozzle size.• Check fuel pump pressure setting.• GPO-199 . . . . . . . . . . . 110 psig (758 kPa)
21If the problem is not getting a spark to ignite the oil, check for the following:1. Loose wiring.2. Red ignition transformer.3. Low voltage.4. Crack
22TROUBLESHOOTINGTROUBLE CAUSE REMEDYOil level below intake line in supply tank. Fill tank with oil.Clogged strainer or filter. Remove and clean strai
23COMMERCIAL OIL FIRED WATER HEATERMODEL GPO XX - 199, 245, 315, 385, 455 & 700AND GPO XX - 315A, 385A, 455A & 700AITEM NO. 13ITEM NO. 25REPL
24GPO 86 GPO 86 GPO 84 GPO 75 GPO 75 GPO 69ITEM DESCRIPTION 199 245 315 385(A) 455(A) 700(A)1 ... *Anode ... 183523-4
3FEATURES AND SPECIFICATIONS ... 2APPROVALS ...
4OIL BURNER SPECIFICATIONSThe oil burner nameplate decal includes a series code which identifiesthe major features of the oil burner. The series numbe
5• The discharge opening of the relief valve should always be pipedto an open drain.• Choose the point of major hot water usage, fuel supply and chimn
6• When communicating with outdoors by means of vertical ducts,each opening shall have a free area of not less than one squareinch per 4,000 Btu per h
7MULTIPLE HEATER FLUESWhen two or more oil-fired water heaters are connected to a single chimneyor vent there shall be sufficient draft available for
8A TYPICAL HEATER INSTALLATION - FIGURE 9Refer to pages 2, 3, and 4 in this manual for more information aboutburner series numbers and characteristics
9BURNERThe burner assembly is mounted on the flange of the combustion chamber, fig. 13.NOTE: Be certain combustion chamber opening is aligned with op